FLUKE - Bộ Datalogger công suất 3 pha Fluke 1735
Model: Fluke 1735
Hãng sản xuất: FLUKE – MỸ
Tính năng Bộ Datalogger công suất 3 pha Fluke 1735:
- Record power and associated parameters for up to 45 days
 
- Monitor maximum power demand over user-defined averaging periods
 
- Prove the benefit of efficiency improvements with energy consumption tests
 
- Measure harmonic distortion caused by electronic loads
 
- Improve reliability by capturing voltage dips and swells from load switching
 
- Easily confirm instrument setup with color display of waveforms and trends
 
- Measure all three phases and neutral with included 4 flexible current probes
 
- View graphs and generate reports with included Power Log software
 
- Compact, rugged design with IP65 case, 600 V CAT III and two-year warranty
 
Thông số kỹ thuật Bộ Datalogger công suất 3 pha Fluke 1735:
Specifications 
 | 
General 
 | 
Display: 
 | 
 ¼ VGA Graphic Color transmissive displays 320 x 240 Pixel with additional background lighting and adjustable contrast, text and graphics in color 
 |  
Quality: 
 | 
 Developed, designed and manufactured according to DIN ISO 9001 
 |  
Memory: 
 | 
 4 MB Flash memory, 3.5 MB for measuring data 
 |  
Interface: 
 | 
 RS-232 SUB-D socket; 115.2 k Baud, 8 data bits, no parity, 1 stop bit, firmware updates are possible with the RS- 232 interface (9-pole extension cable) 
 |  
Sample rate: 
 | 
 10.24 kHz 
 |  
Line frequency: 
 | 
 50 Hz or 60 Hz, user-selectable, with automatic synchronization 
 |  
Power supply: 
 | 
 NiMH battery-pack, with ac adapter (15 V to 20 V/0.8 A) 
 |  
Operation time with battery: 
 | 
 Typical > 12 hours without backlight and > 6 hours with backlight high 
 |  
Dimensions: 
 | 
 240 mm x 180 mm x 110 mm 
 |  
Weight: 
 | 
 1.7 kg, including battery 
 |  
 
 | 
Ambient conditions 
 | 
Working temperature range: 
 | 
 -10 °C to +50 °C 
 |  
Storage temperature range: 
 | 
 -20 °C to +60 °C 
 |  
Operating temperature range: 
 | 
 0 °C to +40 °C 
 |  
Reference temperature range: 
 | 
 23 °C ± 2 °C 
 |  
Note: 
 | 
 The above terms are defined in European Standards. To calculate     the specification at any point in the working temperature range, use the temperature coefficient below. 
 |  
Temperature coefficient: 
 | 
 ± 0.1 % of the measured value per °C from the reference 
 |  
Intrinsic error: 
 | 
 Refers to reference temperature, maximum deviation is guaranteed for two years 
 |  
Operating error: 
 | 
 Refers to operating temperature range, maximum deviation is guaranteed for two years 
 |  
Climatic class: 
 | 
 C1 (IEC 654-1) -5 °C to +45 °C, 5% to 95% RH, no dew 
 |  
Housing: 
 | 
 Cycoloy shock and scratch proof thermoplast V0-type (non-flammable) with rubber protection holster 
 |  
 
 | 
EMC 
 | 
Emission: 
 | 
 IEC/EN 61326-1:1997 class B 
 |  
Immunity: 
 | 
 IEC/EN 61326-1:1997 
 |  
 
 | 
Safety 
 | 
Safety: 
 | 
 IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 2 
 |  
Protection: 
 | 
 IP65; EN60529 (refers only to the main housing without the battery compartment) 
 |  
 | 
 RMS values are measured with a 20 ms resolution. 
 |  
 
 | 
V-rms wye measurement 
 | 
Measuring range: 
 | 
 57 V/66 V/110 V/120 V/127 V/220 V/230 V/240 V/260 V/277 V/347 V/380 V/400 V/417 V/480 V ac 
 |  
Intrinsic error: 
 | 
 ± (0.2% of measured value + 5 digits) 
 |  
Operating error: 
 | 
 ± (0.5% of m. v. + 10 digit) 
 |  
Resolution: 
 | 
 0.1 V 
 |  
 
 | 
V-rms delta measurement 
 | 
Measuring range: 
 | 
 100 V/115 V/190 V/208 V/220 V/380 V/400 V/415 V/450 V/480 V/600 V/660 V/690 V/720 V/830 V ac 
 |  
Intrinsic error: 
 | 
 ± (0.2% of m. v. + 5 digit) 
 |  
Operating error: 
 | 
 ± (0.5 % of m. v. + 10 digit) 
 |  
Resolution: 
 | 
 0.1 V 
 |  
 
 | 
A-rms measurement 
 | 
Flexi set I ranges: 
 | 
 15 A/150 A/3000 A rms (at sine) 
 |  
Current clamp ranges: 
 | 
 1 A/10 A 
 |  
Resolution: 
 | 
 0.01 A 
 |  
Ranges 
 | 
 150 A/3000 A and 1 A/10 A 
 |  
Intrinsic error: 
 | 
 ± (0.5 % of m. v. + 10 digit) 
 |  
Operating error: 
 | 
 ± (1 % of m. v. + 10 digit) 
 |  
Ranges 
 | 
 15 A 
 |  
Intrinsic error: 
 | 
 ± (0.5 % of m. v. + 20 digit) 
 |  
Operating error: 
 | 
 ± (1 % of m. v. + 20 digit) 
 |  
 | 
 The errors of the current probes are not considered. 
 |  
 
 | 
By using Flexi-Set 
 | 
Flexi Set measuring error: 
 | 
 ± (2% of m. v. + 10 digit) 
 |  
Position influence: 
 | 
 ± (3 % of m. v. + 10 digit) 
 |  
CF (typical): 
 | 
 2.83 
 |  
Note: 
 | 
 When using Flexi Set please make sure to position the conductor opposite to the Flexi Set-lock 
 |  
 
 | 
Power measurement (P - Active, S - Apparent, Q- reactive, D - Distorting 
 | 
Measuring range: 
 | 
 see V rms and A rms measurement 
 |  
 | 
 Power errors are calculated by adding the errors of voltage and current 
 |  
 | 
 Additional error due to power factor PF 
 |  
 | 
 Specified error x (1-[PF]) 
 |  
 | 
 Maximum range with voltage range 830 V delta-connection and 3000 A current range is 2.490 MW, higher displayed values possible when using PTs and CTs with ratio feature 
 |  
Intrinsic error: 
 | 
 ± (0.7 % of m.v. +15 digit) 
 |  
Resolution: 
 | 
 1 kW 
 |  
Operating error: 
 | 
 ± (1.5 % of m.v. + 20 digit) 
 |  
 | 
 Typical range with voltage range 230 V wye connection and 150 A current range is 34.50 KW. 
 |  
Intrinsic error: 
 | 
 ± (0.7 % of m.v. +15 digit) 
 |  
Resolution: 
 | 
 1 W to 10 W 
 |  
Operating error: 
 | 
 ± (1.5 % of m.v. + 20 digit) 
 |  
 | 
 The errors of the current sensors themselves have not been considered. 
 |  
 
 | 
Energy measurement (kWh, KVAh, kVARh) 
 | 
Intrinsic error: 
 | 
 ± (0.7 % of m.v.+ F variation error* + 15 digit) 
 |  
Resolution: 
 | 
 1 W to 10 W 
 |  
Operating error: 
 | 
 ± (1.5 % of m.v. + F variation error* + 20 digit) 
 |  
 | 
 *Frequency variation error 
 |  
 
 | 
PF (Power factor) 
 | 
Range: 
 | 
 0.000 to 1.000 
 |  
Resolution: 
 | 
 0.001 
 |  
Accuracy: 
 | 
 ±1 % of full scale 
 |  
 
 | 
Frequency measurement 
 | 
Measuring range: 
 | 
 46 Hz to 54 Hz and 56 Hz to 64 Hz 
 |  
Intrinsic error: 
 | 
 ± (0.2 % of m. v. + 5 digit) 
 |  
Operating error: 
 | 
 ± (0.5 % of m. v.+ 10 digit) 
 |  
Resolution: 
 | 
 0.01 Hz 
 |  
 
 | 
Harmonics 
 | 
Measuring range: 
 | 
 To 50th harmonic (< 50 % of nom) 
 |  
 
 | 
Accuracy 
 | 
Vm, Im, THDV, THDI: 
 | 
 IEC 61000-4-7:2002, Class II 
 |  
Vm ≥ 3% Vn: 
 | 
 ± 5% Vm 
 |  
Vm < 3 % Vnom: 
 | 
 ±0.15% Vnom 
 |  
Im ≥ 10 % Inom: 
 | 
 ± 5% Im 
 |  
Im < 10 % Inom: 
 | 
 ± 0 5% Inom 
 |  
THDV: 
 | 
 for THD < 3% ± 0.15% at Vnom for THD ≥ 3% ± 5% at Vnom 
 |  
THDI: 
 | 
 for THD < 10% ± 0.5% at Inom for THD ≥ 10% ± 5% at Inom 
 |  
Vnom: 
 | 
 Normal voltage range 
 |  
Inom: 
 | 
 Nominal current range 
 |  
 | 
 Vm and Im are measured values of harmonic m 
 |  
 
 | 
Events 
 | 
 | 
 Detection of voltage dips, voltage swells and voltage interruptions with a 10 ms resolution and measuring error of the half period sine wave of rms. 
 |  
Intrinsic error: 
 | 
 ± (1% of m.v. + 10 digit) 
 |  
Operating error: 
 | 
 ± (2% of m.v. + 10 digit) 
 |  
Resolution: 
 | 
 0.1 V 
 |  
 
 | 
 