Thứ Năm, 14 tháng 1, 2016

FLUKE - Máy phân tích chất lượng điện Fluke 434-II Model: Fluke 434-II

FLUKE - Máy phân tích chất lượng điện Fluke 434-II
Model: Fluke 434-II
Hãng sản xuất: FLUKE – MỸ

                                 Kết quả hình ảnh cho Fluke 434-II  FLUKE
Tính năng Máy phân tích chất lượng điện Fluke 434-II:
  • Energy loss calculator: Classic active and reactive power measurements, unbalance and harmonic power, are quantified to pinpoint the fiscal costs of energy losses.
  • Troubleshoot real-time: Analyze the trends using the cursors and zoom tools.
  • Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
  • Measure all three phases and neutral: With included four flexible current probes with enhanced thin flex design to fit into the tightest places.
  • Automatic trending: Every measurement is always automatically recorded, without any set-up.
  • System-monitor: Ten power quality parameters on one screen according to EN50160 power quality standard.
  • Logger function: Configure for any test condition with memory for up to 600 parameters at user defined intervals.
  • View graphs and generate reports: With included analysis software.
  • Battery life: Seven hours operating time per charge on Li-ion battery pack.
Thông số kỹ thuật Máy phân tích chất lượng điện Fluke 434-II:
Product specifications

Model
Measurement range
Resolution
Accuracy
Volt
Vrms (ac+dc)
434-II
1 V to 1000 V phase to neutral
0.1 V
± 0.5% of nominal voltage**** 
Vpk

1 Vpk to 1400 Vpk
1 V
5% of nominal voltage
Voltage Crest Factor (CF)

1.0 > 2.8
0.01
± 5 %
Vrms½
434-II
1 V to 1000 V phase to neutral
0.1 V
± 1% of nominal voltage 
Vfund
434-II
1 V to 1000 V phase to neutral
0.1 V 
± 0.5% of nominal voltage
Amps (accuracy excluding clamp accuracy)
Amps (ac +dc)
i430-Flex 1x 
5 A to 6000 A
1 A
± 0.5% ± 5 counts
i430-Flex 10x
0.5 A to 600 A
0.1 A
± 0.5% ± 5 counts
1mV/A 1x
5 A to 2000 A
1A
± 0.5% ± 5 counts
1mV/A 10x
0.5 A A to 200 A (ac only)
0.1 A
± 0.5% ± 5 counts
Apk
i430-Flex 
8400 Apk 
1 Arms
± 5 %
1mV/A
5500 Apk
1 Arms
± 5 %
A Crest Factor (CF)

1 to 10
0.01
± 5 %
Amps½
i430-Flex 1x 
5 A to 6000 A 
1 A 
± 1% ± 10 counts 
i430-Flex 10x
0.5 A to 600 A
0.1 A 
± 1% ± 10 counts
1mV/A 1x  
5 A to 2000 A 
1A 
± 1% ± 10 counts
1mV/A 10x
0.5 A A to 200 A (ac only)
0.1 A
± 1% ± 10 counts
Afund
i430-Flex 1x 
5 A to 6000 A
1 A
± 0.5% ± 5 counts 
i430-Flex 10x 
0.5 A to 600 A
0.1 A
± 0.5% ± 5 counts
1mV/A 1x 
5 A to 2000 A
1A
± 0.5% ± 5 counts
1mV/A 10x 
0.5 A A to 200 A (ac only)
0.1 A
± 0.5% ± 5 counts
Hz
Hz
Fluke 434 @ 50 Hz nominal 
42.50 Hz to 57.50 Hz
0.01 Hz 
± 0.01 Hz
Fluke 434 @ 60 Hz nominal
51.00 Hz to 69.00 Hz
0.01 Hz
± 0.01 Hz
Power
Watts (VA, var)
i430-Flex 
max 6000 MW
0.1 W to 1 MW
± 1% ± 10 counts
1 mV/A
max 2000 MW
0.1 W to 1 MW
± 1% ± 10 counts
Power factor (Cos j/DPF)

0 to 1
0.001
± 0.1% @ nominal load conditions
Energy
kWh (kVAh, kvarh)
i430-Flex 10x
Depends on clamp scaling and V nominal
± 1% ± 10 counts
Energy loss
i430-Flex 10x
Depends on clamp scaling and V nominal
± 1% ± 10 counts Excluding line resistance accuracy
Harmonics
Harmonic order (n)

DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-harmonic order (n)

OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts
%f
0.0 % to 100 %
0.1 %
± 0.1% ± n x 0.1 %
%r
0.0 % to 100 %
0.1 %
± 0.1% ± n x 0.4 %
Absolute
0.0 to 1000 V
0.1 V
± 5% *
THD
0.0 % to 100 %
0.1 %
± 2.5 %
Amps
%f
0.0 % to 100 %
0.1 %
± 0.1% ± n x 0.1%
%r
0.0 % to 100 %
0.1 %
± 0.1% ± n x 0.4 %
Absolute
0.0 to 600 A
0.1 A
± 5% ± 5 counts
THD
0.0 % to 100 %
0.1 %
± 2.5 %
Watts
%f or %r 
0.0 % to 100 %
0.1 %
± n x 2%
Absolute
Depends on clamp scaling and V nominal 
± 5% ± n x 2 % ± 10 counts
THD
0.0 % to 100 %  
0.1 %
± 5 %
Phase Angle
-360° to +0°
± n x 1°
Flicker
Plt, Pst, Pst(1min) Pinst

0.00 to 20.00
0.01
± 5 %
Unbalance
Volts
%
0.0 % to 20.0 %
0.1 %
± 0.1 %
Amps
%
0.0 % to 20.0 %
0.1%
± 1 %
Mains signaling
Threshold levels

Threshold, limits and signaling duration is programable for two signaling frequencies
Signaling frequency

60 Hz to 3000 Hz
0.1 Hz

Relative V%

0 % to 100 %
0.10 %
± 0.4 %
Absolute V3s (3 second avg.)

0.0 V to 1000 V
0.1 V
± 5 % of nominal voltage

General specifications
Case
Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
Display
Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
Memory
8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size)
Real-time clock
Time and date stamp for Trend mode, Transient display, System Monitor and event capture

Environmental
Operating temperature
0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery
Storage temperature
-20 °C ~ +60 °C
Humidity
+10 °C ~ +30 °C: 95% RH non-condensing 
+30 °C ~ +40 °C: 75% RH non-condensing
 
+40 °C ~ +50 °C: 45% RH non-condensing
Maximum operating altitude
Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V 
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
 
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility (EMC)
EN 61326 (2005-12) for emission and immunity
Interfaces
mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
Warranty
Three years (parts and labor) on main instrument, one year on accessories