Tính năng Thiết bị đo điện trở cách điện Fluke 1507/1503:
 
  
  
   
    
    
     
      
      
       
        
        
- Insulation test range:
 
- 1507: 0.01 MΩ to 10 GΩ
 
- 1503: 0.1 MΩ to 2000 MΩ
 
 
- Insulation test voltages:
 
- 1507: 50 V, 100 V, 250 V, 500 V, 1000 V
 
- 1503: 500 V, 1000 V
 
 
- Save both time and money with Automatic calculation of
             Polarization Index and Dielectric Absorption Ratio (only available
             on the1507)
 
- Make repetitive tests simple and easy with the 1507’s Compare
             (Pass/Fail) function (only available on the 1507)
 
- Repetitive or hard-to-reach testing is easy with the remote
             test probe
 
- Live circuit detection prevents insulation test if voltage
             > 30 V is detected for added user protection
 
- Auto-discharge of capacitive voltage for added user protection
 
- AC/DC voltage: 0.1 V to 600 V
 
- 200 mA Continuity
 
- Resistance: 0.01 Ω to 20.00 kΩ
 
- Save battery power with auto power off
 
- Read measurements easily with large, backlit display
 
- CAT IV 600 V overvoltage category rating for added user
             protection
 
- Remote probe, test leads, probes and alligator clips included
             with each tester
 
- Accepts optional Fluke TPAK magnetic hanging system to free
             your hands for other work
 
- Four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least
             1000 insulation tests
 
- One year warranty
 
 
 | 
        
 
 | 
      
 
 | 
    
 
 | 
   | 
 
Thông số kỹ thuật Thiết bị đo điện trở cách điện Fluke
1507/1503:
 
  | 
   
AC/DC Voltage Measurement 
 | 
 
  | 
   
Accuracy 
 | 
  
  
   
    | 
     
Range 
 | 
    
     
 600.0 V 
 | 
    
    | 
     
Resolution 
 | 
    
     
 0.1 V 
 | 
    
    | 
     
50 Hz to 400 Hz ± (% of Rdg + Digits) 
 | 
    
     
 ± (2 % + 3) 
 | 
    
 
 | 
 
  | 
   
Input impedance 
 | 
  
  
 | 
 
  | 
   
Common mode rejection ratio (1 kΩ
  unbalanced): 
 | 
  
  
   
     | 
    
     
 > 60 dB at dc, 50 or 60 Hz 
 | 
    
 
 | 
 
  | 
   
Overload Protection 
 | 
  
  
 | 
 
 
  | 
   
Earth bond resistance measurement 
 | 
 
  | 
   
Range/Resolution 
 | 
  
  
   
    | 
     
20.00 Ω 
 | 
    
     
 0.01 Ω 
 | 
    
    | 
     
200.0 Ω 
 | 
    
     
 0.1 Ω 
 | 
    
    | 
     
2000 Ω 
 | 
    
     
 1.0 Ω 
 | 
    
    | 
     
20.00 kΩ 
 | 
    
     
 0.01 kΩ 
 | 
    
 
 | 
 
  | 
   
Accuracy 
 | 
  
  
 | 
 
  | 
   
Overload Protection 
 | 
  
  
 | 
 
  | 
   
Open Circuit Test Voltage 
 | 
  
  
 | 
 
  | 
   
Short circuit current 
 | 
  
  
 | 
 
 
  | 
   
Insulation specifications 
 | 
 
  | 
   
Measurement Range 
 | 
  
  
   
    | 
     
1507: 
 | 
    
     
 0.01 MΩ to 10 GΩ 
 | 
    
    | 
     
1503: 
 | 
    
     
 0.01 MΩ to 2000 MΩ 
 | 
    
 
 | 
 
  | 
   
Test voltage 
 | 
  
  
   
    | 
     
1507: 
 | 
    
     
 50 V, 100 V, 250 V, 500 V, 1000 V 
 | 
    
    | 
     
1503: 
 | 
    
     
 500 V, 1000V 
 | 
    
 
 | 
 
  | 
   
Test Voltage Accuracy 
 | 
  
  
 | 
 
  | 
   
Short circuit current 
 | 
  
  
 | 
 
  | 
   
Auto Discharge 
 | 
  
  
   
     | 
    
     
 Discharge time < 0.5 second for C = 1 µF or less 
 | 
    
 
 | 
 
  | 
   
Live circuit indicator 
 | 
  
  
   
     | 
    
     
 Inhibit test if terminal voltage > 30 V prior to
    initialization of test 
 | 
    
 
 | 
 
  | 
   
Maximum Capacitive Load 
 | 
  
  
   
     | 
    
     
 Operable with up to 1 µF load 
 | 
    
 
 | 
 
  | 
   
Measure Accuracy: 
 | 
  
  
   
    | 
     
50 V: 
 | 
    
     
 ±(3 % + 5) 
 | 
    
    | 
     
100 V: 
 | 
    
     
 ±(3 % + 5) 
 | 
    
    | 
     
250 V: 
 | 
    
     
 ±(1.5 % + 5) 
 | 
    
    | 
     
500 V: 
 | 
    
     
 ±(1.5 % + 5) 
 | 
    
    | 
     
1000 V: 
 | 
    
     
 ±(1.5 % + 5) to 2000 MΩ,
    ±(10 % + 3) above 2000 MΩ 
 | 
    
 
 | 
 
 
  | 
   
General Specifications 
 | 
 
  | 
   
Maximum voltage applied to any terminal: 
 | 
  
  
 | 
 
  | 
   
Storage Temperature 
 | 
  
  
   
     | 
    
     
 -40 °C to 60 °C (-40 °F to 140 °F) 
 | 
    
 
 | 
 
  | 
   
Operating Temperature 
 | 
  
  
   
     | 
    
     
 -20 °C to 55 °C (-4 °F to 131 °F) 
 | 
    
 
 | 
 
  | 
   
Temperature Coefficient 
 | 
  
  
   
     | 
    
     
 0.05 x (specified accuracy) per °C for temperatures < 18 °C or
    > 28 °C (< 64 °F or > 82 °F) 
 | 
    
 
 | 
 
  | 
   
Relative Humidity 
 | 
  
  
   
     | 
    
     
 0 % to 95 % @ 10 °C to 30 °C (50 °F to 86 °F) 
 | 
    
     | 
    
     
 0 % to 75 % @ 30 °C to 40 °C (86 °F to 104 °F) 
 | 
    
     | 
    
     
 0 % to 40 % @ 40 °C to 55 °C (104 °F to 131 °F) 
 | 
    
 
 | 
 
  | 
   
Vibration 
 | 
  
  
   
     | 
    
     
 Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument 
 | 
    
 
 | 
 
  | 
   
Shock 
 | 
  
  
   
     | 
    
     
 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six
    sides, oak floor) 
 | 
    
 
 | 
 
  | 
   
Electromagnetic compatibility: 
 | 
  
  
   
     | 
    
     
 In an RF field of 3 V/M, accuracy = specified accuracy (EN
    61326-1:1997) 
 | 
    
 
 | 
 
  | 
   
Safety 
 | 
  
  
   
     | 
    
     
 Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO.
    61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600
    V (CAT IV) 
 | 
    
 
 | 
 
  | 
   
Certifications: 
 | 
  
  
   
     | 
    
     
 CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard
    IEC/EN 61010-1 2nd Edition 
 | 
    
 
 | 
 
  | 
   
Batteries 
 | 
  
  
   
     | 
    
     
 Four AA batteries (NEDA 15A or IEC LR6) 
 | 
    
 
 | 
 
  | 
   
Battery Life 
 | 
  
  
   
    | 
     
Insulation test use: 
 | 
    
     
 Tester can perform at least 1000 insulation tests with fresh
    alkaline batteries at room temperature. These are standard tests of 1000 V
    into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds
    off. 
 | 
    
    | 
     
Resistance measurements: 
 | 
    
     
 Tester can perform at least 2500 earth bond resistance
    measurements with fresh alkaline batteries at room temperature. These are
    standard tests of 1 Ω with a duty cycle of 5 seconds on and
    25 seconds off. 
 | 
    
 
 | 
 
  | 
   
Size 
 | 
  
  
   
     | 
    
     
 5.0 cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in
    L) 
 | 
    
 
 | 
 
  | 
   
Weight 
 | 
  
  
 | 
 
  | 
   
IP Rating 
 | 
  
  
 | 
 
  | 
   
Altitude 
 | 
  
  
   
    | 
     
Operating: 
 | 
    
     
 2000 m CAT IV 600 V, 3000 m CAT III 600 V 
 | 
    
    | 
     
Non-operating (storage): 
 | 
    
     
 12,000 m 
 | 
    
 
 | 
 
  | 
   
Over-range capability: 
 | 
  
  
 | 
 
  | 
   
Included accessories: 
 | 
  
  
   
     | 
    
     
 TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN
    1958646 (black), holster and remote probe 
 | 
    
 
 | 
 
 