FLUKE
- Thiết bị đo điện trở cách điện Fluke 1555/1550C
Model:
Fluke 1555/1550C
Hãng
sản xuất: FLUKE – MỸ
Tính năng Thiết bị đo điện trở cách điện Fluke
1555/1550C:
- Test voltages up to 10 kV provides solutions for
all applications
- CAT III 1000 V, CAT IV 600 V safety rating
- Voltage breakdown detection alerts the user that
voltage is present and gives the voltage reading up to 600 V ac or dc for
increased user safety
- Selectable test voltages in 50 V steps from 250
to 1000 V, and 100 V steps above 1000 V
- Measurements can be stored in up to 99 memory
locations, with each location assigned a unique, user defined, label for
easy recall
- Long battery life gives the user over 750 tests
between charges
- Automatic calculation of Dielectric Absorption
(DAR) and Polarization Index (PI) with no additional setup
- Guard system eliminates the effect of surface
leakage current on high-resistance measurements
- Large digital/analog LCD for easy viewing
- Capacitance and leakage current measurement
- Ramp function for breakdown testing
- Resistance measurements up to 2TΩ
- Timer settings up to 99 minutes for timed tests
- 3-year warranty
Thông số kỹ thuật Thiết bị đo điện trở cách điện Fluke
1555/1550C:
Electrical
specifications
The tester’s accuracy is specified for one year after
calibration at operating temperatures of 0 °C to 35 °C. For operating
temperatures outside the range (-20 °C to 0 °C and 35 °C to 50 °C), add ± .25 %
per °C, except on the 20 % bands add ± 1 % per °C.
Insulation resistance
measurement
|
||
Test voltage (dc)
|
Range (dc)
|
Accuracy (± reading)
|
250 V
|
< 200 kΩ
200 kΩ to 5 GΩ 5 GΩ to 50 GΩ > 50 GΩ |
unspecified
5 % 20 % unspecified |
500 V
|
200 kΩ
200 kΩ to 10 GΩ 10 GΩ to 100 GΩ > 100 GΩ |
unspecified
5 % 20 % unspecified |
1000 V
|
< 200 kΩ
200 kΩ to 20 GΩ 20 GΩ to 200 GΩ > 200 GΩ |
unspecified
5 % 20 % unspecified |
2500 V
|
< 200 kΩ
200 kΩ to 50 GΩ 50 GΩ to 500 GΩ > 500 GΩ |
unspecified
5 % 20 % unspecified |
5000 V
|
< 200 kΩ
200 kΩ to 100 GΩ 100 GΩ to 1 TΩ > 1 TΩ |
unspecified
5 % 20 % unspecified |
10000 V
(1555 only) |
< 200 kΩ
200 kΩ to 200 GΩ 10 GΩ to 2 TΩ > 2 TΩ |
unspecified
5 % 20 % unspecified |
Bar graph range
|
0 to 1 TΩ
|
|
Insulation test voltage accuracy
|
-0 %, +10 % at 1 mA load current
|
|
Induced ac mains current rejection
|
2 mA maximum
|
|
Charging rate for capacitive
load
|
5 seconds per μF
|
|
Discharge rate for
capacitive load
|
1.5 s/μF
|
|
Leakage current
measurement
|
Range: 1 nA to 2 mA
|
Accuracy: ± (5 % + 2 nA)
|
Capacitance
measurement
|
Range: 0.01 uF to 15.00 μF
|
Accuracy: ± (15 % rdg + 0.03 μF)
|
Timer
|
Range: 0 to 99 minutes
|
Resolution Accuracy:
Setting: 1 minute Indication: 1 second |
Live circuit warning
|
Warning Range:
30 V to 660 V ac/dc, 50/60 Hz |
Voltage Accuracy:
± (15 % + 2 V) |
General specifications
|
|
Display
|
75 mm x 105 mm
|
Power
|
12 V lead-acid rechargeable battery, Yuasa NP2.8-12
|
Charger Input (AC)
|
Charger Input (AC) 85 V to 250 V ac 50/60 HZ 20 VA
|
This Class II (double insulated) instrument is supplied with a Class 1
(grounded) power cord. The protective earth terminal (ground pin) is not
connected internally. The extra pin is for added plug retention only.
|
|
Dimensions
|
170 mm x 242 mm x 330 mm (6.7 in x 9.5 in x 13 in)
|
Weight
|
3.6 kg (7.94 lb)
|
Temperature (operating)
|
-20 ºC to 50 ºC (-4 ºF to 122 ºF)
|
Temperature (storage)
|
-20 ºC to 65 ºC (-4 ºF to 149 ºF)
|
Humidity
|
80 % to 31 ºC decreasing linearly to 50 % at 50 ºC
|
Altitude
|
2000 m
|
Enclosure sealing
|
IP40
|
Input overload protection
|
1000 V ac
|
Electromagnetic compatibility
|
EN 61326
|
Certifications
|
![]() ![]() ![]() |
Safety compliance
|
CAT III 1000 V, CAT IV 600 V
|
Pollution degree
|
2
|