FLUKE
– Thiết bị đo đa năng Fluke 1654B
Model:
Fluke 1654B
Hãng
sản xuất: FLUKE – MỸ
Tính năng Thiết bị đo đa năng Fluke 1654B:
Safer, easier installation testing.
The 1654B Installation
Tester verifies the safety of electrical installations in domestic, commercial
and industrial applications. It can ensure that fixed wiring is safe and
correctly installed to meet the requirements of IEC 60364, HD 384 and all
relevant local standards
Faster
- Two
measurements at once and a dual display. PEFC/PSC and loop impedance are
measured and displayed in parallel, saves you more than 50% of test time
compared to other loop testers.
- Additional
new high current loop mode. Faster measurements compared to loop tests
with non-trip mode for RCD’s.
- Unique
zero adapter for fast, always reliable and accurate test lead and mains
cord compensation.
- Fast
voltage measurement between L-N, L-PE and N-PE using the mains cord. No
need to change measurement connections.
|
Safer
- Earth
Volt Touchpad detects raised earth voltages >50 V, indicating
potential dangerous situations.
- Supplied
with the SureGrip™ test leads and clips which gives the user a
comfortable, reliable grip
|
Easy
- Rotary
dial knob indicates clearly which function is selected, all
functionalities on one spot and no complex multi level menus.
- Large
display with backlight, clear symbols with exceptionally wide viewing
angle for easy and safe readings.
- PASS/FAIL
indication for RCD test results.
- Variable
RCD current mode for customized settings.
- Loop
& Line Resistance - mΩ resolution
- Test
smooth dc sensitive RCDs (Type B)
- Extended
Memory
- Extended
documentation mode (UK only)
|
Rugged & lightweight
Withstands a drop of 1 meter.
Compact, lightweight (less than 1.3 kg)
and padded neck-strap to free your hands for all day testing.
Complete kit
All 1650 models are equipped with detachable
leads that can be replaced in case of damage or loss. A durable hard case will
protect your instrument in tough field conditions.
Slim probe design with test button
Keeps your eyes on the panel while probing hard
to reach points. This remote probe is powered by the tester so always operable
(does not require additional batteries).
Zero Adapter
For easy, always reliable and accurate
compensation of test leads and mains cords. This adapter can be used for all
different kind of mains plugs as well as test accessories like probes,
alligator clips etc.
Thông số kỹ thuật Thiết bị đo đa năng Fluke 1654B:
Specifications
|
AC Voltage Measurement
|
Range:
|
500 V
|
Resolution:
|
0.1 V
|
Accuracy (50 - 60 Hz)
|
± (0.8% + 3 digits)
|
Input Impedance
|
3.3 MΩ
|
Overload Protection
|
660 Vrms
|
|
Continuity Testing
|
Range (autoranging):
|
20 Ω, 200 Ω,
2000 Ω
|
Resolution:
|
0.01 Ω, 0.1 Ω, 1
Ω
|
Test Current:
|
> 200 mA
|
Open Circuit Voltage:
|
> 4 V
|
Accuracy:
|
± (1.5%+3 digits)
|
|
Insulation Resistance Measurement
|
Test Voltage:
|
50 - 100 - 250 - 500 - 1000 V
|
Test Voltage:
|
50 V
|
Test Current:
|
1 mA @ 50 kΩ
|
Insulation Range:
|
10 kΩ - 50 мΩ
|
Resolution:
|
0.01 мΩ
|
Accuracy:
|
± (3% + 3 digits)
|
|
|
Test Voltage:
|
100 V
|
Test Current:
|
1 mA @ 100 kΩ
|
Range/Resolution:
|
20 MΩ/0.01 MΩ
|
Range/Resolution:
|
100 MΩ/0.1 MΩ
|
Accuracy:
|
± (3% + 3 digits)
|
|
|
Test Voltage:
|
250 V
|
Test Current:
|
1 mA @ 250 kΩ
|
Range/Resolution:
|
20 MΩ/0.01 MΩ
|
Range/Resolution:
|
200 MΩ/0.1 MΩ
|
Accuracy:
|
± (1.5% + 3 digits)
|
|
|
Test Voltage:
|
500 V
|
Test Current:
|
1 mA @ 500 kΩ
|
Range/Resolution:
|
20 MΩ/0.01 MΩ
|
Range/Resolution:
|
200 MΩ/0.1 MΩ
|
Accuracy:
|
± (1.5% + 3 digits)
|
Range/Resolution:
|
500 MΩ/1 MΩ
|
Accuracy:
|
10%
|
|
|
Test Voltage:
|
1000 V
|
Test Current:
|
1 mA @ 1 MΩ
|
Range/Resolution:
|
20 MΩ/0.01 MΩ
|
Range/Resolution:
|
200 MΩ/0.1 MΩ
|
Accuracy:
|
± (1.5% + 3 digits)
|
Range/Resolution:
|
500 MΩ/1 MΩ
|
Accuracy:
|
10%
|
|
|
Auto Discharge:
|
Discharge time constant, 0.5 second for
C = 1 µF or less
|
Live Circuit Detection:
|
Inhibits test if terminal voltage > 30 V prior to initiation
of test
|
Maximum Capacitive Load:
|
Operable with the 5 µF load
|
|
Loop Impedance Measurement (High Current Mode and Non-Trip Mode)
|
Range:
|
100 - 500 VAC (50/60 Hz)
|
Input connection:
|
Soft Key selection
|
Loop impedance:
|
Phase to earth
|
Line impedance:
|
Phase to neutral
|
Limit on consecutive tests:
|
Automatic thermal shutdown after 50 consecutive tests at 10
second intervals (typical)
|
|
|
Max. Test Current. High Current and Non-Trip Modes:
|
|
Maximum Test Current @ 400 V
|
20 A sinusoidal for 10 ms
|
Maximum Test Current @ 230 V
|
12 A sinusoidal for 10 ms
|
|
|
Range/Resolution:
|
20 Ω/0.01 Ω
|
Range/Resolution:
|
200 Ω/0.1 Ω
|
Range/Resolution:
|
2000 Ω/1 Ω
|
|
|
Accuracy (no Trip mode):
|
± (3% + 6 digits)
|
Accuracy (Hi Current mode):
|
± (2% + 4 digits)
|
|
PFC, PSC Test
|
Computation:
|
PFC or PSC determined by dividing measured mains voltage by
measured loop (L-PE) resistance or line (L-N) resistance
|
Range:
|
0 - 25 kA
|
Resolution (Ik < 1000 A):
|
1 A
|
Resolution (Ik >= 1000 A):
|
0.1 kA
|
Accuracy:
|
Determined by accuracy of loop resistance and mains voltage
measurements.
|
|
RCD Testing ¹
|
G
|
General, no delay
|
S
|
Time delay
|
A
|
Responds to pulsed signal
|
AC
|
Responds to AC
|
B
|
Responds to AC up to 1000 Hz: responds to AC superposed by DC
|
|
Tripping Time Test (ΔT)
|
Trip Time Accuracy
|
±(1% Reading + 1 digit)
|
Multiplier:
|
x ½
|
Current Settings:
|
10, 30, 100, 300, 500, 1000 mA
|
Current Accuracy:
|
+0% - 10%
|
RCD Type ¹:
|
G
|
Measurement Range:
|
310 ms (Europe), 2000 ms (UK)
|
RCD Type ¹:
|
S
|
Measurement Range:
|
510 ms (Europe), 2000 ms (UK)
|
|
|
Multiplier
|
x 1
|
Current Settings:
|
10, 30, 100, 300, 500, 1000 mA
|
Current Accuracy:
|
+10% - 0%
|
RCD Type ¹:
|
G
|
Measurement Range:
|
310 ms
|
RCD Type ¹:
|
S
|
Measurement Range:
|
510 ms
|
|
|
Multiplier:
|
x 5
|
Current Settings:
|
10, 30 mA
|
Current Accuracy:
|
±10%
|
RCD Type ¹:
|
G
|
Measurement Range:
|
50 ms
|
RCD Type ¹:
|
S
|
Measurement Range:
|
160 ms
|
|
Tripping Current (ramp)
|
Current Range:
|
50% - 110% of RCD's rated current
|
Step Size:
|
10% of IΔN
|
Dwell time (Type G): ¹
|
300 ms / step
|
Dwell time (Type S): ¹
|
500 ms / step
|
Trip Current Measurement Accuracy:
|
±5%
|
|
Earth Resistance Test (RE) - Fluke 1653B + 1654B
|
Range/Resolution:
|
200 Ω/0.1 Ω
|
Accuracy:
|
±(2% + 5 digits)
|
Range/Resolution:
|
2000 Ω/1 Ω
|
Accuracy:
|
±(3.5% + 10 digits)
|
Frequency:
|
128 Hz
|
Compliance Voltage:
|
+25 V
|
|
Phase Sequence Indication
|
Icon:
|
Icon Phase Sequence indicator is active
|
Display of Phase Sequence:
|
|
|
Displays ‘1-2-3’ in digital display field for correct sequence.
|
|
Displays ‘3-2-1’ for incorrect phase.
|
|
Dashes in place of a number indicate a valid determination could
not be made.
|
|
Environmental Specifications
|
Operating Temperature
|
|
Humidity (Without Condensation)
|
10 to 30 °C:
|
95%
|
30 to 40 °C:
|
75%
|
|
Safety Specifications
|
Safety Rating
|
|
EN 61010-I CAT III 500V, CAT IV 300V
|
|
Mechanical & General Specifications
|
Size
|
(L x W x H):
|
10 x 25 x 12.5 cm
|
|
Weight
|
|
Batteries
|
|
Warranty
|
|
Battery type
|
|
Alkaline supplied, usable with 1.2V NiCD or NiMH rechargeable
batteries
|
|