FLUKE - Máy ghi chất lượng điện ba pha Fluke 1750 Model: Fluke 1750

FLUKE - Máy ghi chất lượng điện ba pha Fluke 1750
Model: Fluke 1750
Hãng sản xuất: FLUKE – MỸ
                           Kết quả hình ảnh cho Fluke 1750  FLUKE
Tính năng Máy phân tích chất lượng điện Fluke 1750:
  • Power quality that meets the standard: All measurements comply with IEC61000-4-30 standards for correct evaluation of all measured values including voltage, current, power, harmonics, flicker etc.
  • Quick and reliable configuration: ARCHOS 43 Internet Tablet provides a window into what the instrument is recording, enabling quick and reliable configuration even in awkward test locations
  • Threshold-free set up: Apply thresholds after data is collected with Fluke Power Analyze Software – no need to worry about missed information due to incorrect setups
  • Captures everything: Cross-channel and current triggering capture every measurement, on every channel, every time
  • Intuitive PC software: Easily analyze data and generate reports with automated EN50160 reporting and compliance
  • Reporting has never been easier: Auto Report creates either standard reports or customized reports with the minimum effort or hassle. 
  • Plug and play: Set up in minutes with self-identifying current probes and single-lead voltage connections
  • No need to reconnect wires: Swap channels internally with the wireless PDA or PC when connections are not correct
  • Measure every parameter: Voltage and current on three phases, neutral, and ground
  • 5 MHz, 8000 Vpk waveform capture: Get a detailed picture of even the shortest events
  • Quickly retrieve data: With included SD memory card or via the 100BaseT high-speed Ethernet connection.  SD card includes automatic download to SD when no other connection is made to the instrument
Thông sỗ kỹ thuật Máy phân tích chất lượng điện Fluke 1750:
Technical Specifications
Power quality measurement standards
Conformance
 IEC 61999-1-4 Class 1, IEC 61000-4-30 Class A or B depending on measurement function, IEEE519, IEEE1159, IEEE1459 and EN50160
Clock/calendar
 Leap years, 2 4-hour clock
Real-time clock accuracy
 Not more than ± 1 s/day
Internal memory capacity for data
 At least 2 GB
Maximum recording period
 At least 31 days
Measurement time control
 Automatic
Maximum number of events
 Limited only by the size of the internal memory
Power requirements
 100 to 2 40 V rms ± 10 %, 47-63 Hz, 40 W
Operating time during interruptions (internal UPS operation)
 5 minutes per interruption, 60 minutes total operating time without recharging
Dimensions
 215 mm x 310 mm x 35 mm (8.5 in x 12.2 in x 3.5 in)
Mass (weight)
 6.3 kg (14 lb)
Input
Measurement types
 One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta, 21/2 Element Wye
Input channels
 Voltage: 4 channels, ac/dc
 Current: 5 channels
Voltage channels
 Input resistance: 2 MΩ
 Input capacitance: < 2 0 pF
Current input characteristics
 2 V rms = full scale, 1 MΩ Input Impedance for ferro CTs, low impedance for Flexi-CTs
Measuring method
 Simultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal frequency reference used during voltage drops.
Synchronization and sampling
PLL-synchronization source
 The PLL synchronizes to the A-N voltage for wye power types, and to the A-B voltage for delta power types. All listed power types can be characterized as either wye or delta.
PLL lock range
 42.5 to 69 Hz
Sampling frequency
 Voltage and current: 2 56 samples/cycle Inter-harmonics per IEC 61000-4-7: 2 560 points/10 cycles (50 Hz), 3072 points/12 cycles (60 Hz) Transient Voltage: 5 MHz
A/D resolution
 Voltage and current: 2 4 bits
 Transient voltage: 14 bits
Voltage and current measurements
Voltage measurement range
 AC voltage: 1000 V rms ± 10 % over range
 DC voltage: ± 1000 V + 10 % over range
Voltage crest factor
 3 or less
Current measurement range
 Depends on current probe used
Current crest factor
 4 or less
RMS voltage
Measurement type
 True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by IEC 61000-4-30.
Measurement uncertainty
 AC: ± 0.2 % reading ± 0.1 % full scale, above 50 V rms
 DC: ± 0.5 % reading ± 0.2 % full scale, above 50 V dc
RMS current
Measurement type
 True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
Transient voltage (impulse)
Measurement type
 Waveshape sampling
Full scale
 8000 V pk
Sample resolution
 200 nS
Measurement uncertainty
 ± 5 % reading ± 2 0 V (test parameters: 1000 V dc, 1000 V rms, 100 kHz)
Voltage swell (rms swell)
Measurement type
 True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
Displayed data
 Amplitude and duration of swell
Measurement
 Same as rms voltage
Voltage dip (rms sag)
Measurement type
 True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
Displayed data
 Amplitude and duration of dip or interruption
Measurement
 Same as rms voltage
Voltage dropout (interruption)
Measurement type
 Same as voltage dip
LAN interface
Connector
 RJ-45
Speed and type
 10/100 Base-T, auto MDIX
Communications protocol
 TCP/IP over Ethernet
Wireless controller interface
Connection
 wireless (2.4 GHz radio)
Speed
 up to 700 kbit/second
Communications protocol
 Bluetooth SPP
Power Measurements
Power, battery life
Measurement type
 True rms calculated continuously: every cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
Frequency
Measurement range
 42.5 to 69 Hz
Measurement source
 Same as PLL synchronization source
Measurement accuracy
 ± 10 mHz (10 to 110 % of range, with sine wave)
Power Factor
Measurement range
 0.000 to 1.000
Measurement accuracy
 ± 1 digit from the calculation of each measured value (±3 digits for total)
Displacement power factor
Measurement method
 Calculated from the phase difference between voltage fundamental and current fundamental
Measurement range
 - 1.000 (leading) to + 1.000 (lagging)
Measurement accuracy
 ± 0.5 % reading ± 2 % full scale ± 1 digit
Voltage unbalance and phase sequence
Measurement method
 Positive sequence voltage divided by negative sequence voltage, per IEC 61000-4-30
Harmonic voltage and current
Analysis window
 rectangular
Analysis order
 1st to 50th order
Measurement accuracy
 Voltage / Current: 1st to 2 0th orders: ± 0.5 % reading ± 0.2 % full scale, 2 1st to 50th orders: ± 1 % reading ± 0.3 % full scale (current sensor accuracy must be included for current and power)
Measurement method
 IEC 61000-4-7
Inter-harmonic voltage and current (intermediate harmonics)
Analysis window
 rectangular
Analysis orders
 1.5 to 49.5th order
Measurement method
 IEC 61000-4-7
Flicker
Measurement method
 IEC 61000-4-15
 Plt for 2 hours and PSt for 10 minutes
Measuring range:
 0,1 to 5 (25) depending on voltage level, modulation and frequency
Environmental Specifications
Environmental
Operating environment
 Indoors or in covered area outdoors, up to 2 000 m altitude
Storage temperature and humidity
 -20 °C to 50 °C, 80 % RH max, non-condensing
Operating temperature and humidity
 0 °C to 40 °C, 80 % RH max, non-condensing
Maximum rated working voltage
Voltage terminals
 1100 V rms
Voltage durability
 5550 V rms ac for 1 minute, between voltage input terminals, voltage input terminals and current probes, and voltage input terminals and case (50/60 Hz, 1 mA sense current)
Enclosure protection
 IP30 (per EN 60529)
Standards:
EMC
 EN 61326-1:1997+A1:1998 Class A
 EN 61000-3-2:1995+A1:1998+A2:1998
 EN 61000-3-3:1995
Safety
 EN 61010-1 2 nd Edition; 2 000
 Voltage input unit: Contamination Level 2 , Overvoltage Category 1000 V CAT III, 600 V CAT IV (anticipated overvoltage: 8000 V)